- The PFIM RCCB has a compatible shape and is suitable for standard busbar connection with other P series equipment.
- Upper and lower dual-purpose terminal (elevator/door opening)
- Position the optional busbar above or below
- Free terminal space even though busbars are installed
- Universal tripping signal switch, also suitable for PLS., PKN., Z-A. can be mounted later
- Sub-switch Z-HK can be installed later
- Red-green contact position indicator
- Hysteresis type suitable for use with standard fluorescent tubes with or without electric ballast (30mA-RCD: 30 units per phase lead, 100mA-RCD: 90 units per phase lead).
- Note: Depending on the manufacturer of the fluorescent lamp ballast may be more than one part. Favourable symmetrical distribution of fluorescent lamp ballasts on all phases. Consider the displacement references of the fluorescent lamp ballast manufacturer.
- The device works regardless of the installation location
- PKNM-F, 1+N-pole
- Design according to IEC/EN 61009
- Current test marks as printed onto the device
- Line voltage-independent tripping instantaneous 250 A (8/20 μs), surge current proof
- Type G, F 10 ms delay 3 kA (8/20 μs), surge current proof
- Rated voltage 230 V AC, 50 Hz
- Operational voltage range 196-253 V
- Rated tripping current 10, 30, 100, 300 mA
- Rated non-tripping current 0.5 Ian
- Rated insulation voltage 440 VAC
- Sensitivity AC and pulsating DC
- Selectivity class 3
- Rated breaking capacity 10 kA
- Rated current 2 – 40 A
- Rated impulse withstand voltage 4 kV (1.2/50 μs)
- Characteristic B, C
- Maximum back-up fuse (short circuit) 100 A gL (>10 kA)
- Endurance
- electrical components ≥ 4,000 switching operations
- mechanical components ≥ 20,000 switching operations
- Mechanical
- Frame size 45 mm
- Device height 80 mm
- Device width 35 mm (2MU)
- Mounting 3-position DIN rail clip, permits removal from existing busbar system
- Degree of protection, switch IP20
- Degree of protection, built-in IP40
- Upper and lower terminals open mouthed/lift terminals
- Terminal protection finger and hand touch safe, DGUV VS3, EN 50274
- Terminal capacity 1 – 25 mm2
- Terminal torque 2 – 2.4 Nm
- Busbar thickness 0.8 – 2 mm
- Tripping temperature “-25°C to +40°C
- Storage- and transport temperature “-35°C to +60°C
- Resistance to climatic conditions according to IEC/EN 61009
Model | Description |
PFIM-25/2/003 | RCCB PFIM, 25A/2P, 30mA |
PFIM-25/2/01 | RCCB PFIM, 25A/2P, 100mA |
PFIM-25/2/03 | RCCB PFIM, 25A/2P, 300mA |
PFIM-25/4/003 | RCCB PFIM, 25A/4P, 30mA |
PFIM-25/4/01 | RCCB PFIM, 25A/4P, 100mA |
PFIM-25/4/03 | RCCB PFIM, 25A/4P, 300mA |
PFIM-40/2/003 | RCCB PFIM, 40A/2P, 30mA |
PFIM-40/2/01 | RCCB PFIM, 40A/2P, 100mA |
PFIM-40/2/03 | RCCB PFIM, 40A/2P, 300mA |
PFIM-40/4/003 | RCCB PFIM, 40A/4P, 30mA |
PFIM-40/4/01 | RCCB PFIM, 40A/4P, 100mA |
PFIM-40/4/03 | RCCB PFIM, 40A/4P, 300mA |
PFIM-63/2/003 | RCCB PFIM, 63A/2P, 30mA |
PFIM-63/2/01 | RCCB PFIM, 63A/2P, 100mA |
PFIM-63/2/03 | RCCB PFIM, 63A/2P, 300mA |
PFIM-80/2/003 | RCCB PFIM, 80A/2P, 30mA |
PFIM-80/2/01 | RCCB PFIM, 80A/2P, 100mA |
PFIM-80/2/03 | RCCB PFIM, 80A/2P, 300mA |
PFIM-100/2/003 | RCCB PFIM, 100A/2P, 30mA |
PFIM-100/2/01 | RCCB PFIM, 100A/2P, 100mA |
PFIM-100/2/03 | RCCB PFIM, 100A/2P, 300mA |
PFIM-63/4/003 | RCCB PFIM, 63A/4P, 30mA |
PFIM-63/4/01 | RCCB PFIM, 63A/4P, 100mA |
PFIM-63/4/03 | RCCB PFIM, 63A/4P, 300mA |
PFIM-80/4/003 | RCCB PFIM, 80A/4P, 30mA |
PFIM-80/4/01 | RCCB PFIM, 80A/4P, 100mA |
PFIM-80/4/03 | RCCB PFIM, 80A/4P, 300mA |
PFIM-100/4/003 | RCCB PFIM, 100A/4P, 30mA |
PFIM-100/4/01 | RCCB PFIM, 100A/4P, 100mA |
PFIM-100/4/03 | RCCB PFIM, 100A/4P, 300mA |
Tên File File(s)Rev Date